EasyManua.ls Logo

GE POWER/VAC 4.16 - Insulating Primary Cable Terminations

GE POWER/VAC 4.16
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
connection
between
the
cable
and
switchgear
bus
.
A
pothead
also
prevents
seeping
of
oil
from
the
end
of
oil
-
impregnated
varnish
cambric
or
paper
insulated
cable
.
1
.
Remove
rear
bolted
covers
.
2
.
Remove
batten
(
1
)
,
Fig
.
33
.
#
(
b
)
Clamp
-
type
terminals
and
stress
cones
.
No
insulation
materials
are
furnished
for
cable
termin
-
ations
.
When
potheads
are
supplied
as
part
of
switchgear
,
insulation
materials
are
furnished
for
the
bar
terminations
to
the
pothead
studs
.
\
\
\
\
i
o
<
S
1
Batten
S
2
Trough
^
3
Pull
Box
I
L
u
I
I
oo
ON
I
2
00
oo
*
<
CO
00
3
i
Fig
.
33
Installation
of
Primary
Cables
3
.
Remove
cable
trough
cover
and
pull
-
box
cover
.
Fig
.
34
Cable
Termination
without
Pothead
,
Single
Conductor
4
.
Remove
cable
trough
(
2
)
,
Fig
.
33
.
5
.
If
primary
cables
enter
switchgear
from
below
,
termin
-
ate
cables
for
lower
unit
First
.
If
primary
cables
enter
from
above
,
terminate
cables
for
upper
unit
first
.
6
.
Replace
cable
trough
.
7
.
Terminate
primary
cables
in
remaining
unit
.
(
Pulling
cables
thru
cable
trough
.
)
8
.
Replace
pull
-
box
cover
,
cable
trough
cover
,
batten
and
rear
bolted
covers
.
In
all
cases
,
carefully
follow
the
cable
manufacturer
s
recommendations
for
installation
of
the
type
of
cable
being
used
.
A
typical
example
of
terminating
a
shielded
cable
is
shown
in
Fig
.
34
.
If
the
cable
is
aluminum
,
the
conductor
surface
must
be
carefully
abraded
and
the
cable
covered
liberally
with
a
joint
compound
recommended
by
the
cable
manufacturer
.
INSULATING
PRIMARY
CABLE
TERMINATIONS
All
field
-
assembled
joints
for
primary
cable
terminations
should
be
prepared
as
outlined
under
CONNECTIONS
.
Upon
completion
of
the
cable
termination
,
care
must
be
exercised
when
taping
the
exposed
joint
.
1
.
Check
to
see
that
a
sufficient
area
of
insulating
tape
extends
beyond
the
insulation
furnished
on
the
term
-
inal
bars
(
2
inches
for
5
kV
,
3
inches
for
15
kV
)
.
Refer
to
Fig
.
23
.
2
.
All
terminations
should
be
insulated
as
outlined
in
table
,
Fig
.
23
,
for
correct
layers
of
insulation
.
3
.
The
instructions
for
application
of
the
tape
insulation
is
the
same
as
outlined
for
TAPED
JOINTS
.
Before
any
primary
cable
connections
are
made
,
the
cables
should
be
identified
to
indicate
their
phase
relation
-
ship
with
the
switchgear
connections
.
This
is
necessary
to
assure
that
motors
will
rotate
in
the
proper
direction
and
that
the
phase
rotation
is
the
same
when
interconnecting
two
different
sources
of
power
.
There
are
two
common
methods
of
making
primary
cable
connections
:
(
a
)
Potheads
Potheads
are
used
when
it
is
desired
to
hermetically
seal
the
end
of
the
cable
to
make
a
moisture
-
proof
33
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals