GE POWER/VAC 4.16 - Closing Spring Gag Interlock; Key Locks and Padlocks; Auxiliary and Position Switches; Space Heaters

GE POWER/VAC 4.16
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
o
00
m
oo
1
Racking
Nut
2
Bearing
3
Jack
Screw
4
Rail
5
Disconnect
/
Test
Slot
6
Operating
CAM
7
Connect
Slot
op
U
.
Fig
.
43
Closing
Spring
Discharge
Interlock
CLOSING
SPRING
GAG
INTERLOCK
An
interlock
is
provided
at
either
the
front
or
rear
on
the
left
side
of
the
breaker
frame
to
prevent
racking
in
a
breaker
which
has
the
spring
-
blocking
device
(
pin
or
plate
)
in
the
gagged
position
.
The
spring
-
blocking
device
must
be
re
-
moved
so
that
the
interlock
interference
may
reset
to
allow
the
breaker
to
be
racked
.
r
O
PH
O
OO
See
breaker
instruction
book
GEK
90207
or
GEK
90208
for
use
of
the
closing
spring
blocking
device
.
CAUTION
:
Gagging
closing
springs
when
they
are
in
the
discharged
position
can
damage
the
breaker
.
The
breaker
side
frame
may
be
deformed
and
/
or
the
gearmotor
may
be
damaged
.
Fig
.
44
Interference
Interlock
The
second
position
for
padlocks
(
5
)
is
behind
the
key
lock
.
A
padlock
in
this
slot
will
prevent
any
motion
of
the
racking
mechanism
by
keeping
the
hexagon
turning
shaft
covered
.
KEY
LOCKS
On
the
lefthand
breaker
racking
mechanism
track
is
a
provision
for
a
key
lock
.
The
purpose
of
this
lock
is
to
keep
the
breaker
from
closing
in
the
Test
and
Connect
positions
by
operating
the
negative
interlock
see
Fig
.
41
.
To
remove
the
key
(
3
)
,
push
slide
(
1
)
to
the
rear
and
extend
the
bolt
(
4
)
of
the
lock
into
slot
.
This
allows
the
key
to
be
re
-
moved
and
prevents
the
breaker
from
closing
.
The
key
lock
does
not
prevent
motion
of
the
racking
mechanism
.
STATIONARY
AUXILIARY
SWITCH
An
auxiliary
switch
can
be
provided
at
the
bottom
of
the
breaker
compartment
so
that
additional
contacts
can
be
actuated
by
the
operation
of
the
breaker
.
The
breaker
will
operate
this
switch
when
it
is
in
the
Test
or
Connect
position
.
See
Fig
.
45
.
BREAKER
POSITION
SWITCH
PADLOCKS
A
position
switch
can
be
provided
at
the
bottom
of
a
breaker
compartment
so
that
it
will
be
operated
by
a
bracket
on
the
breaker
frame
when
the
breaker
is
in
the
Connect
position
.
When
the
breaker
is
withdrawn
,
a
spring
will
re
-
turn
the
switch
to
its
normal
position
.
See
Fig
.
45
.
Two
positions
for
a
possible
3
padlocks
each
are
provided
on
the
racking
mechanism
.
See
Fig
.
42
.
The
front
position
keeps
the
breaker
from
closing
in
the
Test
and
Connect
position
.
To
obtain
this
position
push
slide
(
1
)
Fig
.
42
to
the
rear
and
insert
the
padlock
in
the
slotted
opening
just
forward
of
the
keylock
(
3
)
.
This
gives
the
same
interlocking
functions
as
the
keylock
and
does
not
block
the
motion
of
the
racking
mechanism
.
SPACE
HEATERS
Space
heaters
are
provided
in
all
outdoor
equipment
in
order
to
keep
the
inside
temperature
several
degrees
higher
42
Courtesy of NationalSwitchgear.com