6–16 PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 6: MONITORING
FREQUENCY: This message displays the frequency (in Hz). Frequency is calculated
from the phase A-N voltage (when setpoint
S2 SYSTEM SETUP ÖØ CURRENT/VOLTAGE
CONFIGURATION ÖØ VT WIRING
is “Wye”) or from phase A-B voltage (when setpoint VT
WIRING is “Delta”). A value of “0.00” is shown if there is insufficient voltage applied to
the PQMII’s terminals (less than 30 V on phase A).
FREQ MIN: This message displays the minimum frequency measured as well as the
time and date at which the minimum frequency occurred.
FREQ MAX: This message displays the maximum frequency measured as well as the
time and date at which the maximum frequency occurred.
6.2.8 Pulse Input Counters
PATH: ACTUAL VALUES Ö A1 METERING ÖØ PULSE INPUT COUNTERS
PULSE INPUT 1(4): These messages display the accumulated value based on total
number of pulses counted since the last reset. One switch input pulse is equal to the
value assigned in the
S2 SYSTEM SETUP ÖØ PULSE INPUT ÖØ PULSE INPUT 1(4) VALUE setpoint.
The units shown after the value are as defined in the
PULSE INPUT UNITS setpoint in the
same menu. The displayed value rolls over to “0” once the value “4294967295”
(FFFFFFFFh) has been reached. To use this feature, the “C” (control) option must be
installed and one of the PQMII switch inputs must be assigned to “Pulse Input 1(4)”
function. The switch input will then count the number of closures or openings
depending upon how the switch is configured; see
Switch Inputs on page 5–21 for
details. The minimum timing requirements are shown in FIGURE 6–2: Pulse Input
Timing.
PULSE IN 1+2+3+4: The totalized pulse input value is displayed here. The pulse inputs
totalized is based on the
S2 SYSTEM SETUP ÖØ PULSE INPUT ÖØ PULSE INPUT TOTAL setpoint.
TIME OF LAST RESET: This message displays the time and date when the pulse input
values were last cleared. The
S1 PQMII SETUP ÖØ CLEAR DATA ÖØ CLEAR PULSE INPUT VALUES
setpoint clears the pulse input values.
PULSE INPUT [Z]
COUNTERS
PULSE INPUT 1 =
0 Units
MESSAGE
PULSE INPUT 2 =
0 Units
MESSAGE
PULSE INPUT 3 =
0 Units
MESSAGE
PULSE INPUT 4 =
0 Units
MESSAGE
PULSE INPUT 1+2+3+4
= 0 Units
MESSAGE
TIME OF LAST RESET:
12:00:00am 01/01/95