EasyManua.ls Logo

GE PQM II - Page 27

GE PQM II
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 1: OVERVIEW
PQMII POWER QUALITY METER – INSTRUCTION MANUAL 1–19
APPROVALS
ENVIRONMENTAL
Sinusoidal Vibration IEC60255-21-1 Class 1
Shock & Bump IEC60255-21-2 Class 1
Power magnetic Immunity IEC61000-4-8 Level 4
Pulse Magnetic Immunity IEC61000-4-9 Level 4
Voltage Dip & interruption IEC61000-4-11
0,40,70,% dips,250/
300cycle interrupts
Ingress Protection IEC60529 IP40 front , IP20 Back
Environmental (Cold) IEC60068-2-1 -10C 16 hrs
Environmental (Dry heat) IEC60068-2-2 70C 16hrs
Relative Humidity Cyclic IEC60068-2-30 6day variant 2
EFT IEEE/ANSI C37.90.1 4KV, 2.5Khz
Damped Oscillatrory IEEE/ANSI C37.90.1 2.5KV,1Mhz
Altitude: 2000m (max)
Pollution Degree: II
Overvoltage Category: II
Ingress protection: IP40 Front , IP20 back
APPROVALS
Applicable Council Directive According to
Low voltage directive EN60255-5
CE compliance EMC Directive EN61000-6-2
UL508
North America cULus e83849 NKCR/7 UL1053
C22.2.No 14
ISO
Manufactured under a registered
quality program
ISO9001
Ambient temperatures:
Operating range: -10C to 60C
Humidity:
Operating up to 95% (non condensing) @ 55C (As per
IEC60068-2-30 Variant 2, 6days)