Chapter 7. Detailed Descriptions of EP-19xx Modules
28 RSTi-EP Functional Safety Manual GFK-2956A
Inputs
Safety inputs
2 x 2 channel
Input type
Type 3 as per IEC 61131-2
Inputs for start function
2 (manual start and autostart)
Input type
Type 3 as per IEC 61131-2
Outputs
Safety output (OSSD)
1
Output current
8 A (not for capacitive load)
Overload protection
excess temperature proof and overload-proof, short circuit proof
with external fuse
Turn-off time
20 ms
Turn-on time
< 2 s
Auxiliary outputs
3 x 2
Output current
max. 10 A (only to support the inputs dedicated inputs)
Diagnosis
Module diagnosis
Yes
Individual channel diagnosis
Yes
Supply
Supply voltage
24 V dc +20%/-15% via system bus
External pre-fusing
mandatory: super fast, max. 8 A
Reverse battery protection
Yes
Current consumption (I
IN
in the power segment of
the Network Adapter), typ.
8 mA
Current consumption (IIN in the respective power
segment)
45 mA
General data
Weight
82 g (2.89 oz)
For additional general data, refer to the section, General Contact Information.