EasyManua.ls Logo

GE RSTi-EP - Page 34

GE RSTi-EP
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7. Detailed Descriptions of EP-19xx Modules
30 RSTi-EP Functional Safety Manual GFK-2956A
Error byte 3
3
0
Temperature Error
1
Internal Error (self-test, LDO, etc)
2
Reserved
0
3
Internal diagnostic FIFO full
0
4
Power supply fault
5
Reserved
0
6
Process alarm lost
0
7
Reserved
0
Channel type
4
0-6
Channel type
0x78
7
Reserved
0
Diagnostic bits per
channel
5
Number of diagnostic bits per channel
4
Number of channels
6
Number of similar channels per module
9
Channel error
7
0
Error at channel 0
1
Error at channel 1
2
Error at channel 2
3
Error at channel 3
4
Error at channel 4
5
Error at channel 5
6
Error at channel 6
7
Error at channel 7
Channel error
8
8
Error at channel 8
9-15
Reserved
0
Channel error
9
16-23
Reserved
0
Channel error
10
24-31
Reserved
0
Safety 0
11
0
Input Discrepancy Error
1
Input Pulse Error
2
Input Test Error
3-7
Reserved
0
Safety 1
12
0
Input Discrepancy Error
1
Input Pulse Error
2
Input Test Error
3-7
Reserved
0
Autostart
13
0-7
Reserved
0
Start Key
14
0-7
Reserved
0
Safety 0 Value
15
0
Input Discrepancy Error
1-7
Reserved
0