EasyManua.ls Logo

GE RSTi-EP - Page 70

GE RSTi-EP
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7. LED Indicators and Troubleshooting
66 RSTi-EP Functional Safety Manual GFK-2956A
LED Indicators and Troubleshooting
Attention
In the event of a malfunction occurring on a RSTi-EP station, carry out the
following recommended measures. If the malfunction cannot be fixed, send the
affected product to GE (refer to the section, General Contact Information).
GE does not assume any liability If the base or electronic module has been
tampered with.
Module
LED
Status
Recommended action
EP-1901
Status
LED
Red:
Module has not been snapped
properly
Error in the supply voltage
Channel error
Check that the module has been snapped into place
properly
Check supply voltage:
1. check +24 V input current path
2. check voltage on plug 4.3; in case of cascading 0
V might be properly, therefore this is not an error
Check channel error
Overload at the OSSD output level
Remove cross connection at OSSD
External feed-in recognised from
field side
Measure voltage at OSSD (4.3) vs. GND (4.4) If a
voltage is present, check the wiring.
Attention: safety hazard - Shut down the system and
prevent it from switching on again
Internal error detected
Module might have switched off caused by
overtemperature; check the temperature inside the
switch cabinet
Perform a cold start within 24 hours
If the error has not been fixed, send the module to GE
for a technical examination
Interruption in one of the two
safety loops of a safety circuit for
at least 3 seconds
Check safety circuit for interruptions if an
interruption of the safety channel is not part of the
application
Cross connection between the
safety loops for at least 3 seconds
Check safety circuit for cross connections
1.1
Off: Safety circuit 1 interrupted
Yellow: Safety circuit 1 OK
Check safety circuit 1
4.2
Off: OSSD not active
Yellow: OSSD active, 24 V DC at output
4.3
Green: Feed-in voltage in valid range
Module
LED
Status
Recommended action

Table of Contents