Chapter 7. LED Indicators and Troubleshooting 
 
GFK-2956A  November 2017  67 
Red: 
–  Module has not been snapped 
properly 
–  Error in the supply voltage 
–  Channel error 
–  Check that the module has been snapped into place 
properly 
–  Check the supply voltage: 
1.  check +24 V input current path 
2.  check voltage on plug 4.3; in case of cascading 0 
V might be properly, therefore this is not an error 
–  Check channel error 
–  Overload at the OSSD output level 
–  Remove cross connection at OSSD 
–  External feed-in recognised from 
field side 
–  Measure voltage at OSSD (4.3) vs. GND (4.4). If a 
voltage is present, check the wiring. 
Attention: safety hazard! Shut down the system and 
prevent it from switching on again. 
–  Internal error detected 
–  Module might have switched off caused by 
overtemperature; check the temperature inside the 
switch cabinet 
–  Perform a cold start within 24 hours. 
If the error has not been fixed, send the module to GE 
for a technical examination. 
–  Interruption in one of the two 
safety loops of a safety circuit for 
at least 3 seconds. 
–  Check safety circuit for interruptions if an 
interruption of the safety channel is not part of the 
application 
–  Cross connection between the 
safety loops for at least 3 seconds. 
–  Check safety circuit for cross connections 
Off: Safety circuit 1 interrupted 
Yellow: Safety circuit 1 OK 
Off: Safety circuit 2 interrupted 
Yellow: Safety circuit 2 OK 
Off: SS1 not active 
Yellow: SS1 active, 24 V DC at output 
Off: OSSD not active 
Yellow: OSSD active, 24 V DC at output 
Green: Feed-in voltage in valid range