HOURS/DAY
The number of eBoost™ Operation Mode hours per weekday “Monday to Sunday” is displayed in the
operation mode parameter window (ceiling value).
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
• Date and Time.
• eBoost™ screen how many hours of eBoost™ Operation Mode have been
selected for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter.
eBoost™ Operation Mode is only possible if the UPS load exceeds a minimum
threshold (default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI
mode.