User Manual TLE Series 160 - 500 UL S2B
This screen is displayed only when
(option).
Enabled
This parameter (values Yes/No) enables
or disables the
Mode.
If the value is “Yes” and the current time
is in the interval for the current day, the
eBoost™ Operation Mode is active.
In case of RPA Parallel System
If eBoost™ Operation Mode is currently disabled (No) and Q1 is closed, when
programming it to enable (Yes) the selected configuration will automatically be
propagated to all units in the RPA Parallel System.
The activation / deactivation of eBoost™ Operation Mode is indicated each time in the event list
Inverter function, at least 1 minute of VFI mode must be programmed during the
Yes/No parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in
VFI mode is not respected, the eBoost™ Operation Mode will be disabled.
If the value is “No”, the UPS is normally operating in VFI / double conversion mode at all times.
eBoost™ Operating Mode the eBoost LED
NOTE !
The configuration of the activation schedule can only be updated when eBoost™ Operation
Mode is disabled (Enabled: No).
DAY
For the weekdays from
“Monday to Sunday”, the edit mode (edit day) allows to define time intervals
when the UPS is operating in
eBoost™ Operation Mode. The hour is given in 24-hour format.
: The hour of the day after which the eBoost™ Operation Mode is enabled.
The eBoost™ Operation Mode is enabled until the following “Stop Time” time is reached
(the “Stop Time” time of the same day if this is later than the “Start Time” time, the “Stop
Time” time of the following day otherwise).
: The hour of the day before which the eBoost™ Operation Mode is enabled.
eBoost™ Operation Mode is enabled starting from the preceding “Start Time” time (the “Start Time”
time of the same day if this is earlier than the
“Stop Time” time, the “Start Time” time of the previous
“Start Time” and “Stop Time” maintain the existing mode only in case the previous
command was “Start Time” and the following command will be “Stop Time”.