9.6.6 Checking the function
Check valve stroke and adjust feedback
1. Actuate the valve with compressed air.
2. Check the valve stroke (c), also refer
to table
Valve strokes depending on
size
.
c
3.
INFO
Please take
the operating instructions for the respective control top into account
for adjustment of the feedbacks.
If the strokes are correct, the feedback can be adjusted and checked.
Þ
The valve stroke has been tested.
V
alve strokes depending on size
Valve size Valve stroke [mm]
Metric
25 15
40 24
50 24
65 26
80 26
100 26
Inch OD
1" 11
1.5" 24
2" 24
2.5" 26
3" 26
4" 26
9.6 Installing the valve - 99 / 128