Control Panel Startup / Testing
36 Installation Guidelines For Spark-Ignited Stationary Generators
Before starting, complete the following:
1. Verify generator is OFF.
2. Set generator MLCB (generator disconnect) to
OFF (OPEN).
3. Turn off all breakers supplied by generator.
4. Check engine crankcase oil level and, if necessary,
fill to oil dipstick FULL mark with recommended oil.
Do not fill above FULL mark.
5. Inspect fuel supply. Gaseous fuel lines must have
been correctly purged and leak tested in accor
-
dance with applicable fuel-gas codes. All fuel shut-
off valves in the fuel supply lines must be open.
6. Verify both auxiliary shutdown switches are ON (I).
During initial startup only, generator may exceed normal
number of start attempts and experience an “OVER
-
CRANK” fault. This is due to accumulated air in the fuel
system during installation. Reset control board by press
-
ing OFF button and ENTER button, and restart up to two
more times if necessary. If unit fails to start, contact an
IASD for assistance.

Table of Contents

Other manuals for Generac Power Systems Protector Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems Protector Series and is the answer not in the manual?

Generac Power Systems Protector Series Specifications

General IconGeneral
BrandGenerac Power Systems
ModelProtector Series
CategoryPortable Generator
LanguageEnglish

Related product manuals