0020145065_01 - 09/12 - Glow-worm
14.2 Fault memory
• This menu allows you to display the 10 most recent failure
codes registered by the appliance.
• In order to display the fault code memory, simultaneously
press the buttons
and for more than 7 seconds.
• The screen will display the rst fault "1." (record) and after
"XX" (fault code).
• To display the other faults registered by the appliance, press
the button
or .
• Press button
for more than 3 seconds to exit this menu.
• To erase the fault memory registered by the appliance, consult
the “Installation adjustments” chapter and use code “d.94”.
14.3 Fault codes
i
IMPORTANT:
The faults described in this chapter should be carried
out by a qualied engineer and if needed by the After
Sales Service.
Fault
codes
Description Cause Solution
F00 Flow heating temperature sensor fault Sensor open circuit
• Check the sensor’s connections.
• Check the wiring harness.
• Check the sensor.
F01 Return heating temperature sensor fault
Return heating temperature sensor
disconnected
F10 Flow heating temperature sensor fault Sensor short-circuit
F11 Return heating temperature sensor fault Return heating temperature sensor shorted.
F20 Overheating fault Overheating safety device activated (97°C)
• Check the operation of the pump.
• Check the wiring harness.
• Check that the ow and return heating isolation
valves are open.
F22
Water pressure of the installation (<0.3
bar)
Return water valve closed
Pump disconnected
Leak in the installation
• Fill the installation.
• Purge the installation.
• Check the pump connections.
• Check the ow and return heating sensor
connections.
• Check that there are no leaks.
F23
Maximum temperature dierence
reached between return and ow
heating
Water circulation fault
• Check the ow and return heating sensor
connection.
• Check the pump speed.
F24 Water circulation fault
Malfunction of the pump (excessively rapid
temperature increase)
• Check that the ow and return heating isolation
valves are open.
F26 Fault in gas valve motor. Disconnected or defective cables
• Check the gas valve connections.
• Check the operation of the gas valve.
Check the operation of the condensate pump (option).
F27 Flame detection fault. Abnormal ame detection
• Check the ame detection electrode.
• Check the main board.
• Check the igniter unit.
F28 Ignition fault
No return gas / Insucient gas ow
Gas valve incorrectly adjusted
Defective ring electrode and ame control /
Defective igniter unit
• Check the return gas circuit (gas valve open).
• Check the observe the ame picture and check the
CO
2
setting.
• Check the igniter unit connections.
• Check the state of the electrode (corrosion).
F29 Loss of ame during operation
F32 Incorrect air pressure Incorrect fan speed.
• Check the entire ue system.
• Check the fan’s electrical connections.
F49 EBUS voltage fault
Fault in EBUS line
Short circuit in EBUS connector
• Check that the eBus controls are tted and wired
correctly.
MAINTENANCE
- 28 -

Table of Contents

Other manuals for Glow-worm Easicom 28

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Glow-worm Easicom 28 and is the answer not in the manual?

Glow-worm Easicom 28 Specifications

General IconGeneral
TypeCombi Boiler
Output28 kW
Energy Efficiency RatingA
MountingWall Mounted
Central Heating Output24 kW
Domestic Hot Water Output28 kW
Fuel TypeNatural Gas
Central Heating Max Pressure3 bar

Related product manuals