Fault code Meaning Possible cause
F.85 Fault: Temperature sensor The flow and/or return temperature sensors have been installed on the same
pipe/incorrect pipe
Temperature sensor not connected or is connected incorrectly
F.86 Fault: Underfloor heating contact Underfloor heating contact open, sensor disconnected or defective
F.87 Fault: Electrodes Electrodes not connected or they are connected incorrectly, short circuit in
the cable harness
F.88 Fault: Gas valve Gas valve not connected or it is connected incorrectly, short circuit in the
cable harness
F.89 Fault: Pump Pump not connected or it is connected incorrectly, incorrect pump connec-
ted, short circuit in the cable harness
Connection No communication between the PCB
and the user interface
Electronics defective