3-5
ALARMS
3.3 HIGH FLAMMABLE GAS OVER-RANGE ALARM
Caution: Exposing the LEL sensor to ammable gas
above 100% LEL can damage the sensor.
If the LEL gas reading exceeds 120% LEL, the displayed
value will change to four rising arrows, the tone of the audible
alarm will change, and the visual alarm will ash quickly. The
ashing message ‘DANGER’ alternates with ’OVER RANGE’,
as shown in Fig. 3.3.
Alternates with
Fig. 3.3 Over Range Alarm