Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The
exclamation point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific
risks. When these symbols appear in the body of this manual or on warning labels, refer back to these
Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout
the body of this manual where applicable.
WARNING
FIRE AND EX
PLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. Paint or
solvent flowing through the system can cause static sparking. To help prevent fire or explosion:
• Electrostatic equipment must be used only by trained, qualified personnel who understand
the requirements of this manual.
• Ground all equipment, personnel, object being sprayed, and conductive objects in or close to
the spray location. Resistance must not exceed 1 megohm. See Grounding instructions.
•Donotuse
pail liners unless they are conductive and grounded.
• Always use the required arc detection settings and maintain a safe distance of at least 6
inches (152 mm) between the applicator and the workpiece.
• Stop operation immediately if static sparking or repeated arc detection errors occur. Do not
use equipment until you identify and correct the problem.
•Checka
pplicator resistance and electrical grounding daily.
• Use and clean equipment only in a well ventilated location.
• Always turn off and discharge the electrostatics when flushing, cleaning or servicing
equipment.
• Elimin
ate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and
plasti
c drop cloths (potential static arc).
• Do not plug or unplug power cords or turn lights on or off when flammable fumes are present.
• Keep the spray area clean at all times. Use non-sparking tools to clean residue from the
booth and hangers.
• Keep a
working fire extinguisher in the work location.
• Interlock the gun air and fluid supply to prevent operation unless ventilation air flow is above
the minimum required value.
• Interlock the Electrostatic Controller and fluid supply with the booth ventilation system to
disable operation if the air flow falls below minimum values. Follow your local codes.
ELE
CTRIC SHOCK HAZARD
Thi
s equipment must be grounded. Improper grounding, setup, or usage of the system can
cau
se electric shock.
• Turn off and disconnect power at main switch before disconnecting any cables and before
servicing or installing equipment.
•Con
nect only to grounded power source.
• All electrical wiring must be done by a qualified electrician and comply with all local codes
and regulations.
3A3954B 3