EasyManua.ls Logo

Grant Aerona3 Series - Page 43

Grant Aerona3 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 8: Operation Page 43
(3.0°C)
(4.0°C)
start temperature
hysteresis
Water pump deactivation
Outdoor air temperature
(HP unit built-in sensor)
Water pump ON
OFF
Figure 8-16: Frost protection (outdoor air temperature) - water pump
Table 8-15: Frost protection parameters
Level
Parameter
Function description
Display and input value
Remarks
Group Code Default Min. Max. Unit
I 43 01 Start temperature of frost protection on room air temperature 14.0 0.0 40.0 0.5°C
I 43 02 Hysteresis of room air temperature of frost protection 1.0 0.5 5.0 0.5°C
I 43 11 Start temperature of Frost protection on Outdoor air temperature 4.0 0.0 10.0 0.5°C
I 43 12 Hysteresis of Outdoor air temperature 3.0 0.5 5.0 0.5°C
I 43 14 Hysteresis of Flow water temperature 3.0 0.5 5.0 0.5°C
I 43 21 Start temperature of Frost protection on Flow water temperature 4.0 0.0 10.0 0.5°C
I 43 22 Hysteresis of Flow water temperature 3.0 0.5 5.0 0.5°C
For details of how to access the parameter settings, refer to Section 9.3.
(3.0°C)
(4.0°C)
start temperature
hysteresis
Water pump deactivation
Flow water temperature
Water Pump ON
OFF
Figure 8-17: Frost protection (flow water temperature) - water pump
(1.0°C)
(14.0°C)
Start temperature
hysteresis
Water pump deactivation
Room air temperature
(remote controller built-in sensor)
Water pump ON
OFF
Figure 8-18: Frost protection (room air temperature) - water pump

Table of Contents

Related product manuals