EasyManua.ls Logo

Grant Aerona3 Series - Page 61

Grant Aerona3 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 11: Fault Finding Page 61
Table 11-12: Sensor, temperature outdoor (heat pump)
Temperature (°C) Resistance (k)
0 31
5 24
10 19
15 15
20 12
25 10
30 8.2
35 6.7
40 5.5
45 4.6
50 3.8
55 3.2
Table 11-13: Sensor, temperature discharge (heat pump)
Temperature (°C) Resistance (k)
10 100
20 64
35 33
40 27
50 18
80 6.4
Table 11-14: Sensor, temperature defrost/suction (heat pump)
Sensor temperature DHW tank/thermal store/mix water (Terminal PCB)
Temperature (°C) Resistance (k)
0 29
5 23
10 19
15 15
20 12
25 10
30 8.3
35 6.9
40 5.7
45 4.8
50 4.1
55 3.4
Table 11-15: Sensor, temperature flow and return circulating water (heat
pump)
Temperature (°C) Resistance (k)
0 25
10 16
20 10
30 7.0
40 4.9
50 3.5
60 2.5
Table 11-16: Sensor, temperature outdoor (Terminal PCB)
Temperature (°C) Resistance (k)
-20 107
- 15 79
-10 59
-5 44
0 34
5 26
10 20
15 16
20 13
25 10
30 8.0
35 6.5
40 5.3
45 4.3
50 3.6

Table of Contents