Appendix C - Commissioning - Parameters Record Page 87
I 51 11
Terminal 11-12: thermal store temperature probe
0=disable
1=enable
0
I 51 19
Terminal 19-18 : DHW remote contact
0=disable (Remote controller only)
1=enable
1
I 51 2 0
Terminal 20-21 : ON/OFF remote contact (CH)
Alarm input
0=disable
1=ON/OFF remote contact
1
I 51 28
Terminal 28-29 : Night mode
0=disable
1=enable
0
I 51 30
Terminal 30-31 : Low tariff
0=disable
1=enable
0
I 51 48
Terminal 48
0=disable
1=additional water pump
0
Pump output setting
DIP SW5 - OFF DIP SW6 OFF
DIP SW5 - ON DIP SW6 - OFF
DIP SW5 - OFF DIP SW6 - ON
Level 1 (maximum)
Level 2 (medium)
Level 3 (minimum)
Level 1