5.6 Installation of Refrigerant Piping
5.6.1 Precautions on piping works
 At the site of transport, storage and construction, the two ends of copper pipes shall be sealed with 
plastic sealing caps. Before welding, copper pipes must be cleaned (washing the inner side of pipe with alcohol) 
to ensure no dust and no water in pipeline
 Nitrogen-filled welding shall be used for the welding of copper pipes. Nitrogen pressure shall be 
NJIFP1LWURJHQÀRZFDQEHVHQVHGE\KDQG
 When multiple multi-connected units are installed, refrigerant piping must be marked to avoid confusion 
between pipes of different units.
 A two-way drier shall be mounted at the liquid pipe side at the place where an outdoor unit is connected.
5.6.2 Assemble copper pipes
7KHFRSSHUSLSHVKDOOEHYHUWLFDOO\LQVHUWHGWRWKHVSHFL¿HGOHQJWK7KHFHQWHUOLQHRIWZRDVVHPEOLHVVKDOO
overlap. The position shall be determined for welding. To ensure correct mounting size, do not determine the 
position with your hands, thus to prevent the copper pipe from moving when heated. 
See below for the welding size of copper pipe:
A
B
D
Outer diameter of pipe D(mm)
Minimum depth of 
penetration B(mm)
Clearance between 
pipes A-D
ij 6
0.05~0.21
ijij 7
ij 8
0.05~0.27
ijijij 10
ijij 12
0.05~0.35
ij 14
If the mounting clearance is too large, the diameter of coarse pipe may be reduced to an appropriate value 
WRDFFRUGLQJWRDSSOLFDEOHVSHFL¿FDWLRQVLIDQ\
5.6.3 Installation of branch pipe
7KHEUDQFKSLSHSOD\VWKHIXQFWLRQWRGLYHUWWKHUHIULJHUDQWÀRZ7KHUHIRUHWKHVHOHFWLRQDQGLQVWDOODWLRQ
of branch pipe is very important to the operation of multi-unit. Based on correct selection of branch pipe, the 
EUDQFKSLSHPXVWEHLQVWDOOHGDFFRUGLQJWRLQVWDOODWLRQVSHFL¿FDWLRQV
 Connection schematics for Y-type branch pipe
The connection of Y-type branch pipe is as shown below. The inlet is connected to outdoor unit or previous branch; the outlet is 
connected to indoor unit or next branch. 
Pipe for Site Use
Pipe for Site Use
To other manifold pipe 
or indoor unit
Inlet
Outlet 1
Y-Type Refnet pipe
Outlet 2
Outdoor Unit
,QVWDOODWLRQVSHFL¿FDWLRQVIRUEUDQFKSLSH
Placement of branch pipe
The branch pipe can only placed horizontally. Meanwhile, two branch pipes must be on the same plane. 
The spacing between two branch pipes must be over 800mm, the spacing between two bends must be over 
800mm, and the spacing between branch pipe and bend point must also be over 800mm.