GREE Photovoltaic Direct-driven Inverter Multi VRF Units
100
Function Button Name and Meaning
Indicates the upward selection button.
Indicates the downward selection button.
Indicates the function button, used for function settings.
Indicates the query button, used for function query.
Indicates the skip button.
Indicates the return button, used to return to the upper-level menu.
Indicates the confirmation button.
Indicates the reset button, used to restore factory settings.
1.3.2.2 Introduction to Functions
(1) List of functions
Function
Code
Function
Name
Function Meaning
Remark
Code Meaning
A2
Refrigerant
recovery
operation
Fully or partially recovers refrigerants in a faulty
module or IDU pipeline according to the system
pressure after automatic startup during
—— ——
It can only
be set.
A6
Unit
cooling/heatin
Sets the unit to cooling/heating, single-cooling,
single-heating, or air supply mode for centralized
nA
Cooling/Heat
ing function
It can be set
and queried.
A7
Outdoor silent
Sets different silent modes to meet users' noise
00
No silent
It can be set
A8
Aftersales
vacuuming
mode
Automatically
enables all electronic expansion valves and
electromagnetic valves during maintenance to
guarantee vacuum processing in all pipelines.
—— ——
It can only
be set.
n0
Conservation
control 1
Automatically decreases the power consumption
of the unit according to system operation
parameters.
01
No
automatic
conservation
It can be set
and queried.
n3
Forcible
defrosting
Forcibly enables ODU defrosting operation. —— ——
It can only
be set.
n4
Conservation
control 2
Forcibly decreases
the maximum power consumption of the unit.
00
No capacity
output
limitation
It can be set
and queried.
n5
Indoor unit
project
Prevents IDU project number conflicts when
different refrigerating systems are controlled in a
—— ——
It can only
be set.
n6 Fault query Queries historical fault information of the ODU. —— ——
It can only be
n7
Parameter
Queries real-time operation parameters of the
—— ——
It can only be
n8
Indoor unit
project
Displays project numberes of all IDUs through
ODU operations.
—— ——
It can only be
queried.
n9
Online IDU
Displays the number of online IDUs. —— ——
It can only be
nb
Outdoor unit
bar code
Queries the entire-unit bar code and controller bar
code of ODU.
—— ——
It can only be
queried.