GREE Photovoltaic Direct-driven Inverter Multi VRF Units
46
Total rated capacity of outdoor
modules (multi-modular system)
Pipe between ODU and the first branch of IDU
Gas pipe size mm(in.)
Liquid pipe size mm(in.)
GMV-Y264WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y288WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y312WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y336WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y360WM/C-F(U)
Ф41.3(1-5/8)
Ф19.05(3/4)
5. Manifold at indoor unit side
Manifold at indoor unit side can be selected as per total capacity of downstream indoor unit(s).
Refer to the following table.
R410A Refrigerant System
Total capacity of downstream
indoor unit(s) C (KBtu/h)
Model
Y-type Manifold
C<68 FQ01A/A
68C102 FQ01B/A
102<C239 FQ02/A
239<C FQ03/A
T- type Manifold
C≤136 FQ14/H1
C≤232 FQ18/H1
232<C FQ18/H2