GREE Photovoltaic Direct-driven Inverter Multi VRF Units
47
6. Fitting pipe between manifolds
Pipe size (between two manifolds at indoor unit side) is based on the total capacity of upstream
indoor unit(s).
Total capacity of downstream indoor
unit(s) C(Btu/h)
Dimension of the pipe of indoor branch
Gas Pipe mm(in.) Liquid Pipe mm(in.)
C≤17100 Φ12.7(1/2) Φ6.35(1/4)
17100<C≤48500 Φ15.9(5/8) Φ9.52(3/8)
48500<C≤72000 Φ19.05(3/4) Φ9.52(3/8)
72000<C≤96000 Φ22.2(7/8) Φ9.52(3/8)
96000<C≤144000 Φ28.6(1-1/8) Φ12.7(1/2)
144000<C≤216000 Φ28.6(1-1/8) Φ15.9(5/8)
216000<C≤240000 Φ34.9(1-3/8) Φ15.9(5/8)
240000<C≤336000 Φ34.9(1-3/8) Φ19.05(3/4)
336000<C Φ41.3(1-5/8) Φ19.05(3/4)
7. Fitting pipe between indoor unit and manifold
Manifold should be matched with fitting pipe of indoor unit.
Rated capacity of indoor unit
C(Btu/h)
Pipe between indoor branch and IDU
Gas Pipe mm(in.) Liquid Pipe mm(in.)
C≤9500 Φ9.52(3/8) Φ6.35(1/4)
9500<C≤17100 Φ12.7(1/2) Φ6.35(1/4)
17100<C≤48500 Φ15.9(5/8) Φ9.52(3/8)