Start Up Data Sheet for GREE Split Air-Conditioner—Service and Repair 
Installation Company   
Address   
Telephone & Fax   
Technician Name   
Registration No.   
Client / Company   
Contact Person   
Installation / Appliance DATA 
Model and No.   
Date of Installation / Repair   
Comments / Repair   
Operating Data – Cooling Mode 
Refrigerant Type  R-290 
 
 
  
  
  
  
  
  
   Flammable Refrigerant 
Refrigerant Name  Propane 
Refrigerant charge in kg   0.20 
Suction Pressure P1   
Suction Temp. P1   
Air Temp. entering condenser T3   
Air Temp. leaving condenser T4   
Air Temp. entering evaporator T1   
Air Temp. leaving evaporator T2   
Performance Test:  With appliance commissioning please operate the Split- Air con-
ditioner with HIGH indoor fan speed in mode COOLING for a minimum of 15 Minutes. 
Measure air inlet (T1) and air outlet (T2) temperature at the indoor unit. The tempera-
ture difference should be at least 8 K. 
Electrical Data 
Power Supply (Voltage)   
Overall Ampere Reading   
Current draw Compressor    
Other executions for system commissioning!               Tick box for completion 
Only use correct and reliable tools / equipment for system commissioning! 
Functional AC system check including performance test!   
Check the Ac system for refrigerant leakage!   
Check that electrical connections are tight!   
Check that condensate drain is tight and with down-grade!    
Check insulation of refrigerant transfer tubes and quick-coupler!   
Check free run of condenser and evaporator fans!   
Check system operation (indoor/outdoor) on abnormal operational noise!   
Clean system components including air filter (if indicated)   
Check display of the remote controller!   
Execute briefing of the AC system user!   
Company signature and date: 
 
 
Client signature and date: