58
Air to Water Heat Pump
Service Manual- Versati II Series
INSTALLATION
Note:
Distance between the indoor unit and the remote air temperature senor should be less than 15 meter
due to length of the connection cable of remote air temperature sensor;
Height from oor is approximately 1.5 meter;
Remote air temperature sensor can not be located where the area may be hidden when door is open;
Remote air temperature sensor can not be located where external thermal inuence may be applied;
Remote air temperature sensor should be installed where space heating is mainly applied;
After the Remote air temperature sensor is installed, should be set the value form “0”to“1” at the function
code 1 in the control panel, so as to select remote air temperature to the control point.
2.3.11 Thermostat
Installation of Thermostat is very similar to that of Remote air temperature sensor.
GRS-CQ12Pd/NaB-K(I), GRS-CQ14Pd/NaB-K(I), GRS-CQ16Pd/NaB-K(I) :
26
252421 22
23
X
T3
Heat N
Thermostat
Thermostat
L
(230V)
27 28
Cool Heat NCool L
(24V)
Fig �1
How to Wire Thermostat
(1) Uncover the front cover of the indoor unit and open the control box.
(2) Identify the power specication of the thermostat, if it is 230V , nd terminal block XT3 as NO.21~24 or
NO.23~26; Otherwise, if it is 24V, nd terminal block XT3 as NO.25~28 or NO.27~30;
(3) If it is Heating/Cooling thermostat, please connect wire as Fig 1 ;
CAUTION!
NEVER USE 230V AC and 24V AC Thermostat at the same time, otherwise, it will cause short-circuit
and power cut-off by circuit breaker;
Setting temperature by Thermostat(heating or cooling) should be chosen within the setting temperature
range of the product ;
For other constrains, please refer to previous page where constrains about remote air temperature
sensor
Do not connect external electric loads, Wire (L) and (N) should be used only for operation Electric type
thermostat.
Never connect external electric loads such as valves, fan coil units, etc. If connected, PCB of the indoor
unit can be seriously damaged.
Installation of Thermostat is very similar to that of Remote air temperature sensor.