Microprocessor Controller for DOAS 51
®
Large Board Points
Binary Values - Read Only
High_Low_Press_
Circ_A_Alarm.Active
High Low Pressure Switch
Alarm Circuit A
Alarm Normal 733 BV
ReadCOV_
NoWrite
0 10682 Discrete
High_Low_Press_
Circ_B_Alarm.Active
High Low Pressure Switch
Alarm Circuit B
Alarm Normal 734 BV
ReadCOV_
NoWrite
0 10683 Discrete
High_Low_Press_
Circ_C_Alarm.Active
High Low Pressure Switch
Alarm Circuit C
Alarm Normal 735 BV
ReadCOV_
NoWrite
0 10684 Discrete
High_Low_Press_
Circ_D_Alarm.Active
High Low Pressure Switch
Alarm Circuit D
Alarm Normal 736 BV
ReadCOV_
NoWrite
0 10685 Discrete
Greentrol_1_Alarm.
Active
Greentrol Device Alarm Alarm Normal 737 BV
ReadCOV_
NoWrite
0 10686 Discrete
Greentrol_2_Alarm.
Active
Greentrol Device Alarm Alarm Normal 738 BV
ReadCOV_
NoWrite
0 10687 Discrete
Greentrol_3_Alarm.
Active
Greentrol Device Alarm Alarm Normal 739 BV
ReadCOV_
NoWrite
0 10688 Discrete
Medium Board Points
Analog Inputs - Read Only
Mixed_Temp_Analog_
Input
Mixed Temperature 35 AI
ReadCOV_
NoWrite
0.1 30263 Input 2
Exhaust_Fan_Speed_
Analog_Input
Exhaust Fan Speed Remote
Command Analog Input
value
143 AI
ReadCOV_
NoWrite
1 30455 Input 2
Supply_Fan_Speed_
Analog_Input
Supply Fan Speed Remote
Command Analog Input
value
155 AI
ReadCOV_
NoWrite
1 30461 Input 2
Binary Inputs - Read Only
Comp_Circ_A_High_
Pressure_Digital_Input
Circuit A High Pressure
Switch
Active Inactive 3 BI
ReadCOV_
NoWrite
0 10052 Discrete
Comp_Circ_A_Low_
Pressure_Digital_Input
Circuit A Low Pressure
Switch
Active Inactive 4 BI
ReadCOV_
NoWrite
0 10053 Discrete
Comp_Circ_B_High_
Pressure_Digital_Input
Circuit B High Pressure
Switch
Active Inactive 5 BI
ReadCOV_
NoWrite
0 10054 Discrete
Comp_Circ_B_Low_
Pressure_Digital_Input
Circuit B Low Pressure
Switch
Active Inactive 6 BI
ReadCOV_
NoWrite
0 10055 Discrete
Drain_Pan_Alarm_
Digital_Input
Drain Pan Alarm Digital
Input Status
Active Inactive 21 BI
ReadCOV_
NoWrite
0 10070 Discrete
EAD_End_Switch_
Digital_Input
Exhaust Air Damper End
Switch Digital Input Status
Active Inactive 22 BI
ReadCOV_
NoWrite
0 10071 Discrete
OAD_End_Switch_
Digital_Input
OAD End Switch Digital
Input Status
Active Inactive 52 BI
ReadCOV_
NoWrite
0 10101 Discrete
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE