2. If connect with some special load,like water pump,its rate power should be below
1.5kw(connect with SPF5000TL HVM model),because normally it needs 3 times of
rate power when it startup.
3.18 warning 38
Fault description:Discharge over current.
Analysis:
1. Battery discharge current is high.
Suggestions:
1. Check load capacity if it’s over battery maximum output current,please disconnect
some load if it’s.
3.19 warning 39
Fault description:Charge over current.
Analysis:
1. Battery charging current is over battery accepted charging current.
Suggestions:
1. check pv panels configuration if it’s really high,for SPF5000TL HVM model,suggest
connect with 3 pcs in series,4 parallel(330W panel).
2. Check battery specification,whether it’s suitable for inverter model or not.
3. Ask battery supplier for help.
3.20 warning 40
Fault description:Discharge over temperature.
Analysis:
1. Battery discharge current is high.
Suggestions:
1. Check load capacity if it’s over battery maximum output current,please disconnect
some load if it’s.