12
2. If connect with some special loadlike water pumpits rate power should be below
1.5kwconnect with SPF5000TL HVM modelbecause normally it needs 3 times of
rate power when it startup.
3.18 warning 38
Fault description:Discharge over current.
Analysis
1. Battery discharge current is high.
Suggestions:
1. Check load capacity if it’s over battery maximum output currentplease disconnect
some load if it’s.
3.19 warning 39
Fault description:Charge over current.
Analysis
1. Battery charging current is over battery accepted charging current.
Suggestions:
1. check pv panels configuration if it’s really highfor SPF5000TL HVM modelsuggest
connect with 3 pcs in series4 parallel330W panel.
2. Check battery specificationwhether it’s suitable for inverter model or not.
3. Ask battery supplier for help.
3.20 warning 40
Fault description:Discharge over temperature.
Analysis
1. Battery discharge current is high.
Suggestions:
1. Check load capacity if it’s over battery maximum output currentplease disconnect
some load if it’s.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF3000TL HVM and is the answer not in the manual?

Growatt SPF3000TL HVM Specifications

General IconGeneral
Rated Power3000W
Input Voltage230V AC
Output Voltage230V AC
Efficiency93%
Dimensions330 x 485 x 135 mm
Weight12 kg
Max. PV Array Power4000W
Max. Charging Current60A
Max. AC Charging Current30A
Max. Solar Charging Current60A
Number of MPP Trackers1
Output Frequency50/60Hz
CommunicationRS232