3.9 warning 15
Fault description:Parallel input utility grid different.
Analysis
1. There may be some phases lost in three phase system.
Suggestions:
1. Check your AC iutput cable wiring connectionall inverters neutral line should connect
to the same neutral line togetherP1 phase inverters should connect to L1 line
togetherP2 phase inverters should connect to L2 line togetherP3 phase inverters
should connect to L3 line together.
3.10 warning 16
Fault description:Parallel input phase error.
Analysis
1. There may be some phases lost in three phase system.
Suggestions:
1. Check AC input cable wiring connectionsmake sure NL1L2L3 lines connected
wellthere are details shown in the user manualpower connection and
communication connection.
3.11 warning 17
Fault description:Parallel onput phase loss.
Analysis
1. There may be some phases lost in three phase system.
Suggestions:
1. Check your AC output cable wiring connectionall inverters neutral line should
connect to the same neutral line togetherP1 phase inverters should connect to L1
line togetherP2 phase inverters should connect to L2 line togetherP3 phase
inverters should connect to L3 line together.
3.12 warning 20
Fault description:Bms communication error.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF3000TL HVM and is the answer not in the manual?

Growatt SPF3000TL HVM Specifications

General IconGeneral
Rated Power3000W
Input Voltage230V AC
Output Voltage230V AC
Efficiency93%
Dimensions330 x 485 x 135 mm
Weight12 kg
Max. PV Array Power4000W
Max. Charging Current60A
Max. AC Charging Current30A
Max. Solar Charging Current60A
Number of MPP Trackers1
Output Frequency50/60Hz
CommunicationRS232