9.3 CIM status register block
Registers in this block can be read by means of function codes
0x03 and/or 0x04. They are read-only. This block can be used for
various kinds of fault finding.
9.4 GSM real time clock
Address Register name Description
00021 GENIbusCRCErrorCnt Holds a CRC error counter for the GENIbus connection between CIM and CU 36X.
00022 GENIbusDataErrorCnt Holds a CRC error counter for the GENIbus connection between CIM and CU 36X.
00023 VersionNumber A Grundfos-specific version number. This is an unsigned integer value.
00024 ActualModbusAddress
Holds the current Modbus slave address of the device.
Valid value range: 1…247. Not used for CIM 500.
00025
00026
GENIbusTXcountHI
GENIbusTXcountLO
Holds a transmit counter for total number of telegrams sent to the CU 36X on the
GENIbus connection.
00027
00028
GENIbusRXcountHI
GENIbusRXcountLO
Holds a receive counter for total number of telegrams received from the CU 36X on the
GENIbus connection.
00029
GeneralStatus
Bit 0: ScadaPinCodeEnabled
PIN code functionality.
0: No PIN code required
1: PIN code required to perform remote control and configuration.
Activation of SCADA PIN code protection takes place via the SMS command
SCADACODE. See "CIM 250 SMS commands" (supplement to installation and
operating instructions) on the CD-ROM supplied with the GSM module.
GeneralStatus
Bit 1: WriteAccess
Remote write access.
0: No write access (the PIN code is incorrect).
1: Full write access (the PIN code is either correct or not enabled).
00030 UnitFamily Grundfos product family.
00031 UnitType Grundfos product type.
00032 UnitVersion Grundfos product version.
00033 GSMBatteryState
State of GSM battery
0: Battery not present
1: Battery must be replaced
2: Battery charging
3: Battery needs charging, but temperature too high
4: Battery needs charging, but temperature too low
5: Battery low
6: Battery OK
255: Battery state not available
00034 ProductSoftwareVersionHI Product software version (BCD diget 1-4 aa.bb)
00035 ProductSoftwareVersionLO Product software version (BCD diget 5-8 cc.dd)
00036 ProductSoftwareDayMonth Product software date (BCD ddmm)
00037 ProductSoftwareYear Product software date (BCD yyyy)
Address Register name Description
CIM
200
CIM
250
CIM
500
00080 SetUNIXRealTimeClockHI
Set real time clock (32 bit UNIX format)
Triggered on value change
- -
00081 SetUNIXRealTimeClockLO - -
00082 SetRtcSecond Set real time clock (seconds) - -
00083 SetRtcMinute Set real time clock (minutes) - -
00084 SetRtcHour Set real time clock (hours) - -
00085 SetRtcDay Set real time clock (day) - -
00086 SetRtcMonth Set real time clock (month) - -
00087 SetRtcYear Set real time clock (year) - -
00088 Bit 0: SetRtc Triggers setting of real time clock (s/m/h/d/m/y format) - -
00089 StatusUNIXRealTimeClockHI
Real time clock (32 bit UNIX format)
- -
00090 StatusUNIXRealTimeClockLO - -
00091 StatusRtcSecond Real time clock - seconds - -
00092 StatusRtcMinute Real time clock - minutes - -
00093 StatusRtcHour Real time clock - hours - -
00094 StatusRtcDay Real time clock - day of month - -
00095 StatusRtcMonth Real time clock - month - -
00096 StatusRtcYear Real time clock - year (after 2000) - -
00097 Bit 0: StatusSetRTCAck Acknowledge of Set RTC command - -