9.17 Hour log register block
Generally the Modbus master application can select the relevant
log series and the relevant number of hours back in time.
Typically several communication sessions (request telegrams)
are needed to read the data.
The communication interface ensures that logged data is
protected against internal update during the time it is accessed
from Modbus, so that the Hour log constitutes a time-consistent
block (data coherency). Every time the real-time clock increments
by one hour, all the logged data in the hour log is shifted one hour
back in time (and the oldest data set is cleared). The exact time
where this happens will be delayed a few seconds relative to the
hour incrementation, so to be sure to read hour log data that has
been correctly updated, we recommend reading data at least 30
seconds after the hour incrementation.
Address Register name Scale Description
02001-02072 PitOverflowTimeHourLog1…72 1 minute Pit, incremental overflow time, hour log 1…72.
02073-02144 PitOverflowCntHourLog1…72 Unscaled Pit, incremental number of overflows, hour log 1…72.
02145-02216 PitOverflowVolumeHourLog1…72 0.1 m
3
Pit, incremental overflow volume, hour log 1…72.
02217-02288 PitSpecificEnergyHourLog1…72 1 Wh/m
3
Pit, specific energy, hour log 1…72.
02289-02360 PitVolumeHourLog1…72 0.1 m
3
Pit, incremental pumped volume, hour log 1…72.
02361-02432 PitEnergyHourLog1…72 0.1 kWh Pit, incremental energy consumption, hour log 1…72.
02433-02504 Pit2PumpsOprTimeHourLog1…72 1 minute
Pit, incremental operating time (two pumps operating simultaneously),
hour log 1…72.
02505-02576 Pit3PumpsOprTimeHourLog1…72 1 minute
Pit, incremental operating time (three pumps operating
simultaneously), hour log 1…72.
02577-02648 Pit4PumpsOprTimeHourLog1…72 1 minute
Pit, incremental operating time (four pumps operating simultaneously),
hour log 1…72.
02649-02720 Pit5PumpsOprTimeHourLog1…72 1 minute
Pit, incremental operating time (five pumps operating simultaneously),
hour log 1…72.
02721-02792 Pit6PumpsOprTimeHourLog1…72 1 minute
Pit, incremental operating time (six pumps operating simultaneously),
hour log 1…72.
02793-02864 Pump1OprTimeHourLog1…72 1 minute Pump 1, incremental operating time, hour log 1…72.
02865-02936 Pump1StartCntHourLog1…72 Unscaled Pump 1, incremental number of starts, hour log 1…72.
02937-03008 Pump1AvgFlowHourLog1…72 0.1 litre/s Pump 1, average flow, hour log 1…72.
03009-03080 Pump1AvgCurrentHourLog1…72 0.1 A Pump 1, average current, hour log 1…72.
03081-03152 Pump2OprTimeHourLog1…72 1 minute Pump 2, incremental operating time, hour log 1…72.
03153-03224 Pump2StartCntHourLog1…72 Unscaled Pump 2, incremental number of starts, hour log 1…72.
03225-03296 Pump2AvgFlowHourLog1…72 0.1 litre/s Pump 2, average flow, hour log 1…72.
03297-03368 Pump2AvgCurrentHourLog1…72 0.1 A Pump 2, average current, hour log 1…72.
03369-03440 Pump3OprTimeHourLog1…72 1 minute Pump 3, incremental operating time, hour log 1…72.
03441-03512 Pump3StartCntHourLog1…72 Unscaled Pump 3, incremental number of starts, hour log 1…72.
03513-03584 Pump3AvgFlowHourLog1…72 0.1 litre/s Pump 3, average flow, hour log 1…72.
03585-03656 Pump3AvgCurrentHourLog…72 0.1 A Pump 3, average current, hour log 1…72.
03657-03728 Pump4OprTimeHourLog1…72 1 minute Pump 4, incremental operating time, hour log 1…72.
03729-03800 Pump4StartCntHourLog1…72 Unscaled Pump 4, incremental number of starts, hour log 1…72.
03801-03872 Pump4AvgFlowHourLog1…72 0.1 litre/s Pump 4, average flow, hour log 1…72.
03873-03944 Pump4AvgCurrentHourLog…72 0.1 A Pump 4, average current, hour log 1…72.
03945-04016 Pump5OprTimeHourLog1…72 1 minute Pump 5, incremental operating time, hour log 1…72.
04017-04088 Pump5StartCntHourLog1…72 Unscaled Pump 5, incremental number of starts, hour log 1…72.
04089-04160 Pump5AvgFlowHourLog1…72 0.1 litre/s Pump 5, average flow, hour log 1…72.
04161-04232 Pump5AvgCurrentHourLog…72 0.1 A Pump 5, average current, hour log 1…72.
04233-04304 Pump6OprTimeHourLog1…72 1 minute Pump 6, incremental operating time, hour log 1…72.
04305-04376 Pump6StartCntHourLog1…72 Unscaled Pump 6, incremental number of starts, hour log 1…72.
04377-04448 Pump6AvgFlowHourLog1…72 0.1 litre/s Pump 6, average flow, hour log 1…72.
04449-04521 Pump6AvgCurrentHourLog…72 0.1 A Pump 6, average current, hour log 1…72.