11.3 Reading the configurable data log series
LogSeriesItemNo
The log series item numbers are shown in the table below. Note
that the scaling of the registers with the present values is
identical to the scaling of the logged data values except for power
values where the scaling has been changed from [1 W] to [10 W]
to fit into 16 bit.
Log series item No Log item register Scale
0001 PitWaterLevel 0.01 m
0002 PitSwitchWaterLevel Unscaled
0003 PitFlowIn 0.1 litre/s
0004 PitAverageFlowIn 0.1 litre/s
0005 PitFlowOut 0.1 litre/s
0006 PitAverageFlowOut 0.1 litre/s
0007 PitPower 10 W*
0008 PitSpecificEnergy 1 Wh/m
3
0010 PitMixerStartPerH Unscaled
0011 PitOutletPressure 0.001 bar
0012 PitEstimatedFlowOut 0.1 litre/s
0500 UserAnalogInput1 0.1 %
0501 UserAnalogInput2 0.1 %
0502 UserAnalogInput3 0.1 %
1000 Pump1Flow 0.1 litre/s
1001 Pump1LatestFlow 0.1 litre/s
1002 Pump1Current 0.1 A
1003 Pump1Insulation 10 kΩ
1004 Pump1WaterInOil 0.1 %
1005 Pump1MotorTemperature1 1 °C
1006 Pump1MotorTemperature2 1 °C
1007 Pump1CosPhi 0.01
1008 Pump1Power 10 W*
1009 Pump1Voltage 0.1 V
1010 Pump1LatestCurrent 0.1 A
1011 Pump1StartsPerH Unscaled
1012 Pump1LatestOperatingTime 1 second
1013 Pump1Frequency 0.01 Hz
1014 Pump1Torque 0.1 Nm
1015 Pump1CurrentAsymmmetry 0.1 %
2000 Pump2Flow 0.1 litre/s
2001 Pump2LatestFlow 0.1 litre/s
2002 Pump2Current 0.1 A
2003 Pump2Insulation 10 kΩ
2004 Pump2WaterInOil 0.1 %
2005 Pump2MotorTemperature1 1 °C
2006 Pump2MotorTemperature2 1 °C
2007 Pump2CosPhi 0.01
2008 Pump2Power 10 W*
2009 Pump2Voltage 0.1 V
2010 Pump2LatestCurrent 0.1 A
2011 Pump2StartsPerH Unscaled
2012 Pump2LatestOperatingTime 1 second
2013 Pump2Frequency 0.01 Hz
2014 Pump2Torque 0.1 Nm
2015 Pump2CurrentAsymmmetry 0.1 %
3000 Pump3Flow 0.1 litre/s
3001 Pump3LatestFlow 0.1 litre/s
3002 Pump3Current 0.1 A
3003 Pump3Insulation 10 kΩ
3004 Pump3WaterInOil 0.1 %