* If ReadWriteSeparation (register 00006, bit 0) is set to "0", the CIM will overwrite this register value with the resulting level.
00176 SetFixedFrequencyPump1 Hz Fixed frequency for pump 1*
00177 SetFixedFrequencyPump2 Hz Fixed frequency for pump 2*
00178 SetFixedFrequencyPump3 Hz Fixed frequency for pump 3*
00179 SetFixedFrequencyPump4 Hz Fixed frequency for pump 4*
00180 SetFixedFrequencyPump5 Hz Fixed frequency for pump 5*
00181 SetFixedFrequencyPump6 Hz Fixed frequency for pump 6*
00182 SetH2SLevel 1 ppm For reception of Hydrogen sulfide (H2S) measurement via GRM
00183
SetH2SSensorFaults
Bit 0: SignalFault
Bool
For reception of H2S sensor signal fault via GRM
0 = No fault
1 = Sensor signal fault
00184 SetDosingRef 0.1 litre/h Set chemical dosing reference for H2S level control