English (GB)
41
00568 Pump4Current 0.1 A Motor current.
00569 Pump4LatestCurrent 0.1 A Latest motor current.
00570 Pump4Voltage 0.1 V Voltage.
00571 Pump4Insulation 10 kΩ Motor insulation resistance.
00572 Pump4WaterInOil 0.1 % Motor water-in-oil measurement.
00573 Pump4Alarms1 Bits See section 11.13 Alarms and warnings
00574 Pump4Alarms2 Bits See section 11.13 Alarms and warnings
00575 Pump4Alarms3 Bits See section 11.13 Alarms and warnings
00576 Pump4Warnings1 Bits See section 11.13 Alarms and warnings
00577 Pump4Warnings2 Bits See section 11.13 Alarms and warnings
00578 Pump4Warnings3 Bits See section 11.13 Alarms and warnings
00579 Pump4MotorTemperature1 1 °C Motor temperature 1.
00580 Pump4MotorTemperature2 1 °C Motor temperature 2.
00581 Pump4PowerHI
1 W Power consumption.
00582 Pump4PowerLO
00583 Pump4EnergyHI
0.1 kWh Energy consumption.
00584 Pump4EnergyLO
00585 Pump4CosPhi 0.01 Motor cos φ.
00586 Pump4Frequency 0.1 Hz Motor-applied frequency.
00587 Pump4VFDmode enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00588 Pump4Torque 0.1 Nm Motor torque.
00589 Pump4Asym 0.1 % Line current asymmetry.
00590
Pump4Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump4Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00591 Pump4Alarms4 Bits See section 11.13 Alarms and warnings
00592 Pump4Warnings4 Bits See section 11.13 Alarms and warnings
00593 Pump4AntiBlockingCounter Bits Number of anti blockings in the pump
00594 Pump4AISetpointSelect enum
Analog input used as setpoint for pump 4:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00595 Pump4SetpointType enum
Setpoint type for pump 4:
0 = Fixed value
1 = Analog input
00596 Pump4FeedbackSensorType enum
Feedback sensor type for pump 4:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00597 Pump4ControlMode enum
Control mode for pump 4:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00598 Pump4ActualSetpoint 1 % Actual setpoint for pump 4
00599 Pump4FixedFrequency 0.01 Hz Fixed frequency for pump 4
Address Register name Scale Description