EasyManuals Logo

Grundfos CIU 501 User Manual

Grundfos CIU 501
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
13.12 Starting the E-pump
This section shows how to start the E-pump.
In the example, slave address 0x01 is used.
Set the ControlRegister to the following values:
Bit 0: 1 (set the E-pump to remote mode)
Bit 1: 1 (start the E-pump)
Bit 2: 0 (do not send a reset fault command)
Bit 3: 0 (direction: clockwise rotation)
Bit 4: 0 (do not copy remote settings to local)
Bits 5-15: 0 (reserved values)
Hence the value to set is 0b0000000000000011: 0x0003.
Request from master to slave
Field Value Description
Slave address 0x01 -
Function code 0x06 Write single register
Start address HI 0x00
ControlRegister address:
00101 (0x0065)
Start address LO 0x64
Value HI 0x00
ControlRegister value:
3 (0x0003)
Value LO 0x03
Example of response from slave to master
Field
Value Description
Slave address 0x01 -
Function code 0x06 Write single register
Start address HI 0x00
ControlRegister address:
00101 (0x0065)
Start address LO 0x64
Value HI 0x00
ControlRegister value:
3 (0x0003)
Value LO 0x03
If there is no response from the slave, see section CIM/CIU 200
Modbus communication faults or CIM/CIU 260 3G/4G cellular
communication faults.
Related information
14.1.2 CIM/CIU 200 Modbus communication faults
14.2.2 CIM/CIU 260 3G/4G cellular communication faults
13.13 Stopping the E-pump
This section shows how to stop the E-pump.
In the example, slave address 0x01 is used.
Set the ControlRegister to the following values:
Bit 0: 1 (set the E-pump to remote mode)
Bit 1: 0 (stop the E-pump)
Bit 2: 0 (do not send a reset fault command)
Bit 3: 0 (direction: clockwise rotation)
Bit 4: 0 (do not copy remote settings to local)
Bits 5-15: 0 (reserved values)
Hence the value to set is 0b0000000000000001: 0x0001.
Request from master to slave
Field Value Description
Slave address 0x01 -
Function code 0x06 Write single register
Start address HI 0x00
ControlRegister address:
00101 (0x0065)
Start address LO 0x64
Value HI 0x00
ControlRegister value:
1 (0x0001)
Value LO 0x01
Example of response from slave to master
Field
Value Description
Slave address 0x01 -
Function code 0x06 Write single register
Start address HI 0x00
ControlRegister address:
00101 (0x0065)
Start address LO 0x64
Value HI 0x00
ControlRegister value:
1 (0x0001)
Value LO 0x01
If there is no response from the slave, see section CIM/CIU 200
Modbus communication faults or CIM/CIU 260 3G/4G cellular
communication faults.
Related information
14.1.2 CIM/CIU 200 Modbus communication faults
14.2.2 CIM/CIU 260 3G/4G cellular communication faults
41
English (GB)

Table of Contents

Other manuals for Grundfos CIU 501

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CIU 501 and is the answer not in the manual?

Grundfos CIU 501 Specifications

General IconGeneral
BrandGrundfos
ModelCIU 501
CategoryController
LanguageEnglish

Related product manuals