Stop functions
Constant pressure with stop function
The purpose of the stop function is to stop the pump
when low or no flow is detected.
When low flow is detected, the pump is in on/off opera-
tion. If there is flow, the pump will continue operating
accord
ing to the setpoint. See fig. 22.
Fig. 22 Constant pressure with stop function. Difference
between start and stop pressures (ΔH)
Low flow can be detected in two different ways:
a built-in low-flow detection function
a flow switch connected to a digital input.
Low-flow detection function
The low-flow detection function will check the flow reg-
ularly by reducing the speed for a short time. No or only
a small ch
ange in pressure means that there is low flow.
Low-flow detection with flow switch
When a flow switch detects low flow, the digital input
will be activated.
Operating conditions for the stop function
It is only possible to use the stop function if the system
incor
porates these components:
a pressure sensor
a non-return valve
a diaphragm tank.
Note: T
he non-return valve must always be installed
before the pressure sensor. See figs 23 and 24.
Fig. 23 Position of the non-return valve and pressure sen-
sor in a system with suction lift operation
Fig. 24 Position of the non-return valve and pressure sen-
sor in a system with positive inlet pressure
Diaphragm tank
The stop function requires a diaphragm tank of a cer-
tain minimum size. The tank must be installed as close
as
possible after the pump, and the precharge pressure
must be 0.7 x actual setpoint.
Recommended diaphragm tank size:
If a diaphragm tank of the above size is installed in the
system, the factory setting of ΔH is the correct setting.
If the tank installed is too small, the pump will start and
stop too often.
TM03 8477 1607
Stop pressure
ΔH
Start pressure
Continuous operation
On/off operation
TM03 8582 1907TM03 8583 1907
Rated flow rate of pump
gpm (m³/h)
Typical diaphragm tank size
gal (litres)
0-25 (0-6) 2 (8)
25-100 (7-24) 4 (18)
100-175 (25-40) 14 (50)
175-300 (41-70) 32 (120)
300-450 (71-100) 44 (180)
Pressure sensor
Diaphragm tank
Non-return valve
Pump
Pressure sensor
Pump
Non-return valve
Diaphragm tank

Other manuals for Grundfos CUE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CUE Series and is the answer not in the manual?

Grundfos CUE Series Specifications

General IconGeneral
CategoryDC Drives
Output Voltage24 V DC
Control Signal0-10 V, 4-20 mA
CommunicationModbus RTU
Protection FeaturesOvervoltage, overcurrent, overtemperature, short circuit
Humidity5% to 95% (non-condensing)
Enclosure classIP20
Enclosure RatingIP20

Related product manuals