11.2.2 Installing a communication interface module
WARNING
Electric shock
Death or serious personal injury.
- Make sure that other pumps or sources do not
force flow through the pump even if the pump is
stopped. This will cause the motor to act like a
generator, resulting in voltage on the pump.
WARNING
Electric shock
Death or serious personal injury.
- Switch off the power supply for at least 3 minutes
before you start any work on the product. Make
sure that the power supply cannot be accidentally
switched on.
- It must be possible to lock the main switch in
position 0. Type and requirements as specified in
EN 60204-1, 5.3.2.
Step Action Illustration
1
Terminal-connected versions:
Remove the front cover from the control box.
TM05 2875 3416
2
Plug-connected versions:
Open the front cover.
TM05 8458 3416
3 Unscrew the earth connection.
TM06 6907 3416
4
Fit the communication interface module as illustrated and
click it on.
TM05 2914 3416