3 
Table 2 Temperature/humidity requirements in the equipment room 
Model  Operating temperature  Operating humidity 
• H3C MSR810 
{  RT-MSR810-W 
{  RT-MSR810-W-DB 
{  RT-MSR810-LM 
{  RT-MSR810-W-LM 
• H3C MSR810 Series 
{  RT-MSR810 
{  RT-MSR810-LM-
CNDE-SJK 
{  RT-MSR810-10-PoE 
{  RT-MSR810-LM-HK 
{  RT-MSR810-W-LM-
HK 
{  RT-MSR810-LM-GL 
{  RT-MSR810-W-LM-GL 
0°C to 40°C (32°F to 104°F)  5% RH to 90% RH, noncondensing 
• RT-MSR810-LME 
• RT-MSR810-LMS 
• RT-MSR810-LMS-EA 
• RT-MSR810-LUS 
0°C to 40°C (32°F to 104°F)  0% RH to 95% RH, noncondensing 
 
Cleanliness 
Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of 
metal components and contact points, especially when indoor relative humidity is low. In the worst 
case, electrostatic adsorption can cause communication failure.  
Table 3 Dust concentration limit in the equipment room 
Substance  Concentration limit (particles/m
3
) 
Dust particles 
≤ 3 x 10
4
 
(No visible dust on the tabletop in three days) 
NOTE: 
Dust diameter ≥ 5 µm 
 
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion 
and premature aging of components, as shown in Tab le 4 . 
Table 4
 Harmful gas limits in an equipment room 
Gas  Maximum concentration (mg/m
3
) 
SO
2
 0.2 
H
2
S 0.006 
NH
3
 
0.05 
NO
2
 0.04 
Cl
2
 
0.01