Capture Jet
®
Water Wash
Operation & Maintenance & Service Manual
CJOWWM/012009/rev1/EN
VIEWING/CLEARING STATISTICS
• Statistic can be cleared by pressing the Mute key while pressing the statistic key.
• Wash time can be changed easily by a simple procedure
1. Press “WASH TIME SETTING” button on the electronic text display. Currently
set value in minutes is displayed.
2. Press the “ENTER” button, a blinking cursor appears
3. Use the “” up and down arrows to set desired wash time.
4. Press “ENTER” again to nish.
FACTORY DEFAULT VALUES:
The unit has pre programmed default values
FAN OPERATION DURING FIRE
When the unit detects the Fire input, it will shut off the make air and exhaust fan by default according to this parameter. By
program fans can be on, by default exhaust fan is off in the re mode.