11.3 TROUBLESHOOTING - INSPECTION RESULTS with heater on. Heat full on.
Numbers in ( ) are for terminal strips numbered “4, 5, 6, 7, 8, 10.
STEP INSPECT FOR VOLTAGE CHECK PROBABLE CAUSE
NO air flow from exhaust
NO voltage
Circuit breaker tripped. Combustion
air blower shorted out. Replace
combustion air blower.
NO fuel smell from
exhaust
NO voltage
YES air flow
NO voltage
See 11.4.1: Overheat switch
activated. If voltage at pin 2,
overheat condition exists. These
switches are auto-reset. Overheat
switches require a cool down of 3-5
minutes once activated.
If voltage to pin 1 of the switch but
none to pin 3, even after cool down
NO fuel smell
NO voltage
YES air flow out exhaust
YES voltage
See 11.4.4: Adjustable duct switch
(thermostat).
NO fuel smell
NO voltage
YES air flow
YES voltage
See 11.4.5: Cycling switch.
See 11.4.6: Fuel solenoid.
NO fuel smell
YES voltage
YES air flow
YES voltage
YES fuel smell
YES voltage