12
3.3. Installing the Temperature Sensors
Note! Do not install the temperature sensor closer
than 1000 mm to an omnidirectional air vent or
closer than 500 mm to an air vent directed away
from the sensor. See figure 9. The air flow near an
air vent cools down the sensor, which gives inac-
curate temperature readings to the control unit. As
a result, the heater might overheat.
3.3.1. Installing the Temperature Sensor WX232
Check the correct location for the temperature sen-
sor from the heater’s instructions for installation
and use.
Wall-mounted heaters (see figure 7)
• Fasten the temperature sensor on the wall
above the heater, along the vertical centre line
running parallel to the sides of the heater, at a
distance of 100 mm from the ceiling.
Floor-mounted heaters (see figure 8)
• Option 1: Fasten the temperature sensor on the
wall above the heater, along the vertical centre
line running parallel to the sides of the heater,
at a distance of 100 mm from the ceiling.
• Option 2: Fasten the temperature sensor to
the ceiling above the heater, at a distance of
100–200 mm from the vertical centre line of
the heater’s side.
3.3. 感温器安装
注意! 感温器不能置于通风口旁边,气流会降低
感温器感应温度。因而使桑拿炉过热。正确的通
风口与感温器安装间距位置、见 图 9. 全方向
性的通风口最小间距1000毫米、 定向性的通风口
最小间500毫米。
3.3.1. 安装感温器 WX232
从安装与使用说明书检查正确的感温器与桑拿炉
安装位置。
•
感温器安装在桑拿炉垂直中心线上方,
天花板对下100毫米
座地型桑拿炉感温器安装位置 (图8)
•
选择1: 感温器安装在檣侧,桑拿炉中心上方,天花板
对下100毫米。注意!桑拿炉与墙身距离。
•
选择2: 感温器安装在天花板,与桑拿炉侧面的垂直
中心线的距离保持100-200毫米适当水平距离。
Figure 7. The place of the temperature sensors in connection with wall-mounted heaters
图7. 挂墙型桑拿炉感温器安装位置
WX232
150 mm
100 mm
1100 mm
100 mm
WX232
Temperature sensor
感温器
挂墙型桑拿炉感温器安装位置 (图7)
中