INSTALLATION INSTRUCTIONS FOR HERON 2.2
The Heron 2.2 is suitable for installation in most caravans & motorhomes.
Installation in Commercial and Industrial vehicles and equipment should be
referred to AIRCOMMAND AUST for assessment of suitability.
The capacity of the airconditioner to adequately cool or heat a van, is dependent on:
The size of the van
The thickness and quality of thermal insulation installed in the van
The expected outside or ambient conditions.
The HERON 2.2 is recommended for vans up to 5.2 m overall, but assumes that
wall and ceilings are insulated with a minimum of 25 mm of insulation, wool or
foam. Windows should all have shades or curtains as a minimum.
If the van is to be used mainly in extreme conditions (40°C plus), then be
conservative, i.e. ensure the best insulation is installed, consider double glazed
windows, and size the airconditioner down to 4.8 m maximum.
315
440
460
235
Condenser
Question and Answer IconNeed help?

Do you have a question about the HERON 2.2 and is the answer not in the manual?

HERON 2.2 Specifications

General IconGeneral
Cooling Capacity2.2 kW
Power Supply220-240V, 50Hz
Energy Efficiency Ratio (EER)3.2
Air Flow Volume350 m³/h
RefrigerantR410A

Summary

Installation Instructions for Heron 2.2

Description of the Heron 2.2 System

Choosing a Position for the Con/set

Installing the Condenser Set

Marking Out the Floor

Procedure for marking floor holes for condenser unit installation.

Marking Out the Wall

Steps for marking wall openings and preparing for condenser unit.

Positioning of the Con/set

Guidance on placing the condenser unit against the wall for sealing.

Pipe Installation and Control Wiring

Air Handler Installation

Key Installation Points

Three critical points for successful air handler installation.

Cupboard Fitting Procedure

Steps for fitting the air handler into a cupboard with a removable front.

Pipework and Drain Installation

Routing refrigerant pipes and fitting the condensate drain.

Mounting and Final Panel Fit

Connecting power, mounting the unit, and fitting the front panel.

Installing Air Handler in Existing Cupboard

Summary of Air Handler Fitting

Charging the System

Method 1: Purging

Procedure for purging the system using refrigerant gas.

Method 2: Vacuum Pump Evacuation

Procedure for removing non-condensables using a vacuum pump.

Leak Testing

Fitting of Air Handler Facia

Installer Tests Before Delivery

Cooling Test Procedure

Steps to verify cooling function and performance.

Heating Test Procedure

Steps to verify heating function and performance.

Unit Specifications

Trouble Shooting

Insufficient Cooling Issues

Diagnosing and resolving problems with insufficient cooling.

Insufficient Heating Issues

Diagnosing and resolving problems with insufficient heating.

Water Dripping from Air Handler

Troubleshooting water leaks from the air handler unit.