User manual for poly-phase meter
17
9 Billing
9.1 Daily frozen
At least store 62 days data
Freezing time: 00:00 at midnight everyday
Freezing content: Can be configurable, same as load profile list(item 8.2)
Daily freezing profile is the load profile whose period is set as 1440min.
9.2 Monthly billing
Capacity: At least store 13 items of monthly billing data
Automatic billing: When meter passes the preset billing time, the meter will
freeze the monthly billing data automatically. The format is XX day XX hour, and
the default is 00 clock on the first day of each month.
Manual billing: Support sending command or press-button billing. When meter
under scroll button display mode, press the seal button for 10 seconds, and then s
-PrESS-bL shows on display, then press any button and the LCD will display
donE, which means press-button billing has finished. This function support
configuring as enable mode or disable mode. There are delay times between
manual billing to reduce illegal repeat operation in short time.
Support supplement latest one billing data when meter power off or clock adjust.
Support configuring maximum 60 objects one time, the list is as follows:
Clock
Meter serial number
Import active energy
Export active energy
Import active energy in L1
Export active energy in L1
Import active energy in L2
Export active energy in L2
Import active energy in L3
Export active energy in L3
Combined active energy
Reactive energy in QI
Reactive energy in QII
Reactive energy in QIII
Reactive energy in QIV
Reactive energy in QI in L1