X-HART 32 01 3 Product Description
HI 801 307 E Rev. 5.00 Page 31 of 58
3.7 System cable
3.7.1 System Cable X-CA 005
The X-CA 005 system cable is used to wire the X-CB 016 03/04 and X-CB 016 53/54 connector
boards to the field termination assemblies.
General
Cable
LIYY-TP 38 x 2 x 0.25 mm²
Wire
Finely stranded
Average outer diameter (d)
approx. 15.2 mm
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length
8…30 m
Color coding
Based on DIN 47100, see Table 13.
Table 20: Cable Data
Identical Cable Plugs
Figure 10: System Cable X-CA 001 01 n
The system cable is available in the following standard length:
System cable
Description
Length
X-CA 001 01 8
Coded cable plugs on both sides
8 m
X-CA 001 01 15
15 m
X-CA 001 01 30
30 m
Table 21: Available System Cables
3.7.2 Cable Plug Coding
The cable plugs are equipped with three coding pins. Therefore, cable plugs only match
connector boards and FTAs encoded accordingly, see Figure 7.

Table of Contents