4 Start-up X-HART 32 01
Page 42 of 58 HI 801 307 E Rev. 5.00
4.3.3 Tab: I/O Submodule HART_32_01: Channels
The I/O Submodule HART_32_01:Channels tab contains the following system parameters for
each HART channel.
Global variables can be assigned to the statuses and parameters with -> and used in the user
program. The value without -> must be directly entered.
Channel number, defined by default
TRUE: Faultless channel
FALSE: Faulty channel
Activate HART [BOOL] -> BOOL W Activate/deactivate HART communication for this
Table 26: Tab I/O Submodule HART_32_01:Channels in the Hardware Editor
4.3.4 Submodule Status [DWORD]
Coding of the variable Submodule Status.
Fault detected while initializing the module
Chip select monitoring time
Warning, deviation of internal voltage measurement
Deviation of the HART clock to the internal 33 MHz clock
Deviation of the 33 MHz clock
Defective voltage monitoring
Internal voltage on 3V4 is defective
Internal voltage on 1V8 is defective
Internal voltage on 1V2 is defective
Internal voltage on 3V3 is defective
Internal voltage on GND is defective
Internal voltage on SI1 is defective
Internal voltage on SI2 is defective
Internal voltage on MES_WD is defective
Table 27: Submodule Status [DWORD]