X-HART 32 01 4 Start-up
HI 801 307 E Rev. 5.00 Page 39 of 58
4.3.1 Tab: Module
The Module tab contains the statuses and parameters for the module.
Name
R/W
Description
Enter these statuses and parameters directly in the Hardware Editor.
Name
W
Module name
Noise Blanking
W
Noise blanking performed by processor module allowed
(activated/deactivated).
Default setting: Activated
The processor modules defers the reaction to detected
transient faults until the safety time has expired. The user
program retains its last valid process value.
Name
Data type
R/W
Description
The following statuses and parameters can be assigned global variables and used in the user program.
Module OK BOOL R TRUE:
No module fault.
FALSE:
Module fault
Channel fault (no external faults), the module is not inserted.
Observe the Module Status parameter!
Module Status
DWORD
R
Status of the module
Coding
Description
0x00000001
Module fault
1)
0x00000002
Temperature threshold 1 exceeded
0x00000004
Temperature threshold 2 exceeded
0x00000008
Incorrect temperature value
0x00000010
Voltage on L1+ is defective
0x00000020
Voltage on L2+ is defective
0x00000040
Internal voltage is defective
0x80000000
No connection to the module
1)
1)
These faults affect the Module OK status and need
not be separately evaluated in the user program.
Timestamp [µsec]
DWORD
R
Microsecond fraction of the timestamp.
Point in time at which the channel measurement was
performed.
Timestamp [s]
DWORD
R
Second fraction of the timestamp.
Point in time at which the channel measurement was
performed.
Table 24: Module Tab in the Hardware Editor