Error code list
© 2009 Hirschmann Automation and Control GmbH · Branch Office Ettlingen · eMail: info.ecs@hirschmann.de · www.hirschmann.com 44
24 183 19 1012e (Generic) / 2009-02-26 / Rev. 01 / rk.
Error Code Error Cause Elimination
EAD
No valid A2B switch
status
• Sensor wrong function
• CAN bus delay
• Radio telegram delay module
(radio A2B)
• Radio telegram ID is invalid
• Replace A2B switch
• Replace cable to the A2B
switch
• Replace battery of radio module
(radio A2B)
• Setup ID in DGA12.9
EDB
Datalogger setup error
• Setup of the datalogger is
cleared (ser. crane data file or
battery buffered RAM)
• transfer data and setup
datalogger again
EDC
Datalogger watchdog
activated
• datalogger processing time limit
exceeded
• Reset system
• Connect PC terminal and watch
error messages
EDD
Battery empty
• Battery check detected a low
voltage of the battery
• change battery, after this setup
of RTC
EDE
Record lost
• Not possible to save data
because other task saves data
at the same time
• Message disappears after a few
seconds
EDF
Flash block full
• Not possible to save any more
data
• Message disappears after a few
seconds
EFD
LMI Watchdog
extra time
• a function needs more than 0.5
sec, e.g. Flash PROM write
• Message disappears after a few
seconds
NOTE:
If an error message not included in the above list is displayed, please contact Hirschmann Service USA:
www.hirschmann.com > USA > Electronic Control Systems > Contact - ECS.