Part Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
F9
Temperature setting
interlock
X
00 Not available
This function is used to prevent changes to
the temperature setting.
01
Available
(factory setting)
FA
Fan speed selection
interlock
X
00 Not available
This function is used to prevent changes to
the fan speed.
01
Available
(factory setting)
Fb
Automatic louver interlock X
00 Not available
This function is used to prevent changes to
automatic louver operations.
01
Available
(factory setting)
FC
Lower cooling temperature
setting limit
X
00 Standard
This function is used to define a lower
temperature setting limit for FAN/COOL/
DRY functions.
01
Lower limit
+1 °C
02
Lower limit
+2 °C
03-08
Lower limit
+(03-08) °C
09
Lower limit
+9 °C
10
Lower limit
+10 °C
Fd
Upper heating temperature
setting limit
X
00 Standard
This function is used to define an upper
temperature setting limit for the HEAT
function.
01
Lower limit
-1 °C
02
Lower limit
-2 °C
03-08
Lower limit
-(03-08) °C
09
Lower limit
-9 °C
10
Lower limit
-10 °C
FE
Not used –
00 Not available
–
01 Used as setting
for conditions
00
02
FF
ON/OFF timer function
interlock
X
00 Not available
This function is used to lock timer
activation.
01
Available
(factory setting)
H1
Maintenance alarms O
00 Display
This function is used to display or hide
maintenance alarms.
01 Hide
H2
Automatic control
indication
O
00 Display
This function is used to display or hide the
automatic control indication.
01 Hide
6 Optional functions
204
SMGB0063 rev. 1 - 10/2010