Alarm
Code
44
Activation of Low Pressure Increase Protection
●
The alarm code is ashed on the 7-segment display of the outdoor unit.
●
The alarm code is displayed on the wired controller of the indoor unit.
★
If the suction pressure (Ps) of the compressor is more than 1.4 MPa for a minute, the compressor stops. The
operation automatically restarts after three minutes. If this occurs again twice in the next 30 minutes, this
alarm code is displayed.
TROUBLESHOOTING