150
MAINTENANCE
2.9 Reader (DCL)
This part is used for changing the alternative current to the direct current for the inverter.
Model: 3HP~6.5HP
Reactor <400V/50Hz, 380-415V/50Hz, 380V/60Hz>
Items Specications
Character 0.41mH (40KHz) (DC 16A)
Rated Current 16A
Direct Current Resistance 50.0mΩ (Max) (25°C)
Model: 7HP~12HP
Items Specications
Character 1mH
Rated Voltage AC 380V/415V
Rated Current 30A
Red
Red
Black
Black