EasyManua.ls Logo

Hitachi RAS-8.0HNBRMQ1 - Page 164

Hitachi RAS-8.0HNBRMQ1
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
162
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No. 7-Segment Display Setting Item
Contents
11
0
IU Electronic Expansion
Valve Opening during
Heating Operation
Stoppage
No setting
1 Expansion valve opening: pattern1
2 Expansion valve opening: pattern2
12
0
IU Electronic Expansion
Valve Opening during
Heating Thermo-OFF
No setting
1 Expansion valve opening: pattern1
2 Expansion valve opening: pattern2
13
0
IU Electronic Expansion
Valve Opening during
Heating Thermo-ON
No setting
1 Expansion valve opening: pattern1
2 Expansion valve opening: pattern2
14
0
Sound Reduced Function
No setting
1 Low Noise Setting 1
2 Low Noise Setting 2
3 Low Noise Setting 3
4 Low Noise Setting 1
5 Low Noise Setting 2
6 Low Noise Setting 3
7 Low Noise Setting 1
8 Low Noise Setting 2
9 Low Noise Setting 3
15
0
Demand Function Setting
No setting
1 Valid demand function all time
16
0
Demand Function Setting
No setting
1 Valid wave function (20min. 100% demand/10min. minimum setting)
17
0
Protection of Decrease
in Outlet Temperature of
Cooling
No setting
1 Cooling outlet temperature decrease protection1
2 Cooling outlet temperature decrease protection1
18
0
Outlet Temperature Control
(DOAS)
No setting
1 Restrain capacity control
2 Outlet air temperature control
19
0
Not Prepared
1
20
0 Thermo-OFF Setting
for Outdoor Unit After
Defrosting Operation
No setting (continuously operation)
1 Valid forced stoppage after defrost operation
21
0
Intermittent Operation of
Outdoor Fan Motor
(Snow Prevention)
(Prepared 1)
No setting (continuously outdoor fan operation when "input function
No.4"=ON)
1 Intermittent outdoor fan operation (30sec. ON/570sec. OFF)
2 Intermittent outdoor fan operation (60sec. ON/540sec. OFF)
3 Intermittent outdoor fan operation (120sec. ON/480sec. OFF)
4 Intermittent outdoor fan operation (300sec. ON/300sec. OFF)
22
0
Prepared 2
1
23
0
Prepared 3
1

Table of Contents

Other manuals for Hitachi RAS-8.0HNBRMQ1

Related product manuals