EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No. 7-Segment Display Setting Item
Contents
11
0
IU Electronic Expansion
Valve Opening during
Heating Operation
Stoppage
No setting
1 Expansion valve opening: pattern1
2 Expansion valve opening: pattern2
12
0
IU Electronic Expansion
Valve Opening during
Heating Thermo-OFF
No setting
1 Expansion valve opening: pattern1
2 Expansion valve opening: pattern2
13
0
IU Electronic Expansion
Valve Opening during
Heating Thermo-ON
No setting
1 Expansion valve opening: pattern1
2 Expansion valve opening: pattern2
14
0
Sound Reduced Function
No setting
1 Low Noise Setting 1
2 Low Noise Setting 2
3 Low Noise Setting 3
4 Low Noise Setting 1
5 Low Noise Setting 2
6 Low Noise Setting 3
7 Low Noise Setting 1
8 Low Noise Setting 2
9 Low Noise Setting 3
15
0
Demand Function Setting
No setting
1 Valid demand function all time
16
0
Demand Function Setting
No setting
1 Valid wave function (20min. 100% demand/10min. minimum setting)
17
0
Protection of Decrease
in Outlet Temperature of
Cooling
No setting
1 Cooling outlet temperature decrease protection1
2 Cooling outlet temperature decrease protection1
18
0
Outlet Temperature Control
(DOAS)
No setting
1 Restrain capacity control
2 Outlet air temperature control
19
0
Not Prepared
1
20
0 Thermo-OFF Setting
for Outdoor Unit After
Defrosting Operation
No setting (continuously operation)
1 Valid forced stoppage after defrost operation
21
0
Intermittent Operation of
Outdoor Fan Motor
(Snow Prevention)
(Prepared 1)
No setting (continuously outdoor fan operation when "input function
No.4"=ON)
1 Intermittent outdoor fan operation (30sec. ON/570sec. OFF)
2 Intermittent outdoor fan operation (60sec. ON/540sec. OFF)
3 Intermittent outdoor fan operation (120sec. ON/480sec. OFF)
4 Intermittent outdoor fan operation (300sec. ON/300sec. OFF)
22
0
Prepared 2
1
23
0
Prepared 3
1